Flameproof Couplers
|
HCA 400 Flameproof 400AMP 12,000VOLT Bolted Half Couplers and Adaptors |
|
![]() |
|
|
12Kv. Adaptor (Front View) |
12Kv. Adaptor (Rear View) |
|
|
|
12Kv Half Coupler (Front View) |
12Kv Half Coupler (Rear View) |
|
|
|
12Kv Half Coupler and Adaptor (Coupled) |
|
General Technical Specification
Ratings
* Maximum Voltage. Phase to Phase. 12Kv. Insulation Level. 28Kv. R.M.S. for 1 minute. 75Kv. Peak Impulse.
* Maximum Current. 400Amp continuous. Symmetrical fault current. 29,28Ka. For 1 second. I.P. rating. I.P. 68. 1 meter.
Connections available
* Power contacts. 3.
* Earth Contact. 1.
* Auxiliary / Ground check. 1. Standard. 3 Optional.
Cable type accommodated
* Metric type Trailing Cable. 12Kv. 240mm. Sq. maximum.
* Metric type XLPE. Cable. 12Kv. 240mm. Sq. maximum.
* American Shovel / Dragline Cable. 8Kv. 350 SWG. maximum. 15Kv. 4/0 SWG. maximum.
Connector Coupling Types
* Bolted.